Miniature circuit-breaker, Acti9 iC60N, 1P, 6 A, C curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)

Miniature circuit-breaker, Acti9 iC60N, 1P, 6 A, C curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)

0 reviews 0 sold. Only 1 remain
0.00ريال
Product Code: A9F77106
Availability: In Stock
Viewed 616 times

Product Description

This Acti9 iC60N is a low voltage miniature circuit breaker (MCB). It is a 1P circuit breaker with 1 protected pole, 6A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 220VAC to 240VAC conforming to EN/IEC 60947-2 standard and 6000A at 230VAC conforming to EN/IEC 60898-1 standard. It complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker protects circuits against short circuit and overload current. Its unique VisiTrip indicator reduces intervention time by showing the faulty circuit. Its VisiSafe green strip guarantees the physical opening of the contacts to allow downstream maintenance. Its fast closing mechanism independent of manual operation improves its service life. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ui rated insulation voltage is 500VAC. Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost. The product can be clipped on a DIN rail. Its width is 2 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is white (RAL9003). The dimensions are (W) 18mm x (H) 85mm x (D) 78.5mm. The weight is 0.215kg. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is -35°C to 70°C. The storage temperature is -40°C to 85°C.

Item specifics

  • Main

  • Breaking capacity 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
  • Curve code c
  • Device Application Distribution
  • Device short name IC60N
  • Network type AC DC
  • Number of protected poles 1
  • Poles description 1P
  • Product name Acti9 iC60
  • Quality labels NF
  • Range Acti9
  • Standards IEC 60947-2 IEC 60898-1 EN 60898-1 EN 60947-2
  • Suitability for isolation Yes conforming to EN 60898-1 Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2
  • Trip unit technology Thermal-magnetic
  • Utilisation category Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2
  • Product or component type Miniature circuit-breaker
  • Complementary

  • 9 mm pitches 2
  • Colour White
  • Comb busbar and distribution block compatibility Top or bottom: YES
  • Connections - terminals Single terminal (top or bottom) 1…25 mm² rigid Single terminal (top or bottom) 1…16 mm² flexible
  • Contact position indicator Yes
  • Control type Toggle
  • Depth 78.5 mm
  • Earth-leakage protection Without
  • Electrical durability 10000 cycles
  • Height 85 mm
  • Limitation class 3 conforming to EN 60898-1 3 conforming to IEC 60898-1
  • Local signalling Trip indicator
  • Magnetic tripping limit 8 x In +/- 20 %
  • Mechanical durability 20000 cycles
  • mounting mode Fixed
  • Mounting support DIN rail
  • Net weight 0.215 kg
  • network frequency 50/60 Hz
  • Tightening torque 2 N.m top or bottom
  • Width 18 mm
  • Wire stripping length 14 mm for top or bottom connection
  • [Ics] rated service breaking capacity 27 kA 75 % conforming to EN 60947-2 - 12...60 V AC 50/60 Hz 7.5 kA 75 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 27 kA 75 % conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz 7.5 kA 75 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 15 kA 75 % conforming to IEC 60947-2 - 100...133 V AC 50/60 Hz 15 kA 75 % conforming to EN 60947-2 - 100...133 V AC 50/60 Hz 6000 A 100 % conforming to EN 60898-1 - 230 V AC 50/60 Hz 6000 A 100 % conforming to IEC 60898-1 - 230 V AC 50/60 Hz 10 kA 100 % conforming to EN 60947-2 - 72 V DC 10 kA 100 % conforming to IEC 60947-2 - 72 V DC 15 kA 100 % conforming to EN 60947-2 - 12...60 V DC 15 kA 100 % conforming to IEC 60947-2 - 12...60 V DC
  • [In] rated current 6 A
  • [Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2
  • [Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2 500 V AC 50/60 Hz conforming to IEC 60947-2
  • Environment

  • Ambient air temperature for operation -35…70 °C
  • Ambient air temperature for storage -40…85 °C
  • IP degree of protection IP20 conforming to IEC 60529 IP20 conforming to EN 60529
  • Operating altitude 0...2000 m
  • Overvoltage category IV
  • Pollution degree 3 conforming to EN 60947-2 3 conforming to IEC 60947-2
  • Relative humidity 95 % at 55 °C
  • Tropicalisation 2 conforming to IEC 60068-1
  • Packing Units

  • Number of Units in Package 1 1
  • Number of Units in Package 2 12
  • Number of Units in Package 3 132
  • Package 1 Height 1.800 cm
  • Package 1 Length 9.500 cm
  • Package 1 Weight 108.000 g
  • Package 1 Width 7.500 cm
  • Package 2 Height 8.500 cm
  • Package 2 Length 21.900 cm
  • Package 2 Weight 1.356 kg
  • Package 2 Width 9.900 cm
  • Package 3 Height 30.000 cm
  • Package 3 Length 40.000 cm
  • Package 3 Weight 15.421 kg
  • Package 3 Width 30.000 cm
  • Unit Type of Package 1 PCE
  • Unit Type of Package 2 BB1
  • Unit Type of Package 3 S03
  • Contractual warranty

  • Warranty 18 months