Anti Harmonic detuned reactor 50kvar 190Hz (3.8) 7% 50Hz 690V

Anti Harmonic detuned reactor 50kvar 190Hz (3.8) 7% 50Hz 690V

0 reviews 0 sold. Only 1 remain
0.00ريال
Product Code: LVR07500A69T
Availability: In Stock
Viewed 833 times

Product Description

The VarPlus detuned reactor are designed to protect the capacitor by preventing the amplification of the harmonics present in the system. Capacitors and Reactors are configured in Series resonant circuit. Tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system. This reactor is rated for 50 kVar output power with 3.8/190 Hz tuning order at 690V AC at 50 Hz. Relative impedance, 7 %. This component meet the standards IEC 60068. This component require a forced convection, a fan need to be added. The case dimensions are 270mm in height, 260mm in width and 200mm in depth. For a product weight of 22 kg.

Item specifics

  • Main

  • Device short name DR
  • Network Frequency 50 Hz
  • Network rated voltage 690 V AC 50 Hz
  • Range PowerLogic
  • Reactive power rating 50 kvar for 690 V AC 50 Hz
  • Tuning order 3.8 - 190 Hz - 7 % - 50 Hz
  • Product or component type Detuned reactor
  • Complementary

  • Connections - terminals Pad terminal
  • Depth 200 mm
  • Dielectric test voltage 4 kV 50 Hz 1 minute
  • Dynamic withstand current 2.2 x Isc
  • Electrical insulation class Class H
  • Fixing center 200 x 125 mm
  • Fundamental current rating 41.8 A
  • Harmonic current spectrum 3.7 % x I3 38.2 % x I5 13.6 % x I7 4.9 % x I11
  • Height 270 mm
  • Inductance tolerance - 5 % to 5 % per phase
  • Net weight 22 kg
  • power losses (max) 320 W
  • RMS current rating 45.2 A
  • Type of cooling Forced convection
  • Type of installation Indoor installation
  • Value of inductance 2.232 mH
  • Width 260 mm
  • [Imp] maximum permanent current 1.2 x I1
  • [Ith] conventional free air thermal current 2 A at 250 V AC 50 Hz
  • [Ui] rated insulation voltage 1.1 kV
  • Environment

  • Ambient air temperature for operation 0…55 °C at <= 1000 m 0…50 °C at > 1000...2000 m
  • Average ambient air temperature for operation 50 °C at <= 1000 m (average over 24 hours) 40 °C at <= 1000 m (average over 1 year) 45 °C at > 1000...2000 m (average over 24 hours) 35 °C at > 1000...2000 m (average over 1 year)
  • Climatic withstand Relative humidity: 20...80 % Salt mist (400 V/50 Hz) : 250 hours
  • IP degree of protection IP00
  • Operating altitude <= 2000 m
  • Standards IEC 60068
  • Packing Units

  • Number of Units in Package 1 1
  • Number of Units in Package 2 2
  • Package 1 Height 49.000 cm
  • Package 1 Length 60.000 cm
  • Package 1 Weight 28.900 kg
  • Package 1 Width 40.000 cm
  • Package 2 Height 50.000 cm
  • Package 2 Length 80.000 cm