variable speed drive, Altivar Process ATV900, ATV930, 0.75kW, 400 to 480V, with braking unit, IP21

variable speed drive, Altivar Process ATV900, ATV930, 0.75kW, 400 to 480V, with braking unit, IP21

0 reviews 0 sold. Only 1 remain
0.00ريال
Product Code: ATV930U07N4
Availability: In Stock
Viewed 890 times

Product Description


This Altivar Process ATV900 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It is suitable for motors with power rating up to 0.75kW/1hp for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 0.37kW/0.5hp for applications requiring significant overload (up to 150%). It works at a rated supply voltage from 380V to 480V AC. This variable speed / frequency drive (VSD / VFD) is specifically designed for industrial processes. In the following market segments, oil and gas, mining, minerals and metals, food and beverage water and wastewater. It offers high motor performance on any motor and total control of any kind of coupling in master/slave applications. Network services help ensure operation continuity even in case of connection breakdown. Web server and data logging help reduce downtime through fast troubleshooting and preventive maintenance. Its advanced connectivity, including EtherNet/IP and Modbus TCP, allows deep integration into automation architectures. It is designed to be mounted in vertical position (+/- 10 °) on a wall.

Item specifics

  • Main

  • Continuous output current 2.2 A 4 kHz normal duty 1.5 A 4 kHz heavy duty
  • Degree of protection UL type 1
  • Device Application Industrial Application
  • Discrete input logic 16 preset speeds
  • Maximum output frequency 599 Hz
  • Network Frequency 50-60 Hz
  • Nominal switching frequency 4 kHz
  • option module Slot A communication module Profibus DP V1 Slot A communication module PROFINET Slot A communication module DeviceNet Slot A communication module EtherCAT Slot A communication module CANopen daisy chain RJ45 Slot A communication module CANopen SUB-D 9 Slot A communication module CANopen screw terminals Slot A/slot B/slot C digital and analog I/O extension module Slot A/slot B/slot C output relay extension module Slot B 5/12 V digital encoder interface module Slot B analog encoder interface module Slot B resolver encoder interface module communication module Ethernet Powerlink
  • Phase 3 phase
  • Prospective line Isc 50 kA
  • Switching frequency 2...16 kHz adjustable 4...16 kHz with derating factor
  • Synchronous motor control profile Permanent magnet motor Synchronous reluctance motor
  • Variant Standard version With braking chopper
  • Range of product Altivar Process ATV900
  • Product or component type Variable speed drive
  • Product specific application Process for industrial
  • mounting mode Wall mount
  • Communication port protocol Modbus TCP EtherNet/IP Modbus serial
  • [Us] rated supply voltage 380...480 V - 15...10 %
  • Motor power kW 0.75 kW normal duty 0.37 kW heavy duty
  • EMC filter Integrated With EMC plate option
  • IP degree of protection IP21
  • Product destination Asynchronous motors Synchronous motors
  • Line current 1.5 A 380 V normal duty) 0.9 A 380 V heavy duty) 1.3 A 480 V normal duty) 0.8 A 480 V heavy duty)
  • Apparent power 1.1 kVA 480 V normal duty) 0.7 kVA 480 V heavy duty)
  • Maximum transient current 2.6 A 60 s normal duty) 2.3 A 60 s heavy duty)
  • Asynchronous motor control profile Constant torque standard Optimized torque mode Variable torque standard
  • Complementary

  • 4 quadrant operation possible True
  • Acceleration and deceleration ramps Linear adjustable separately from 0.01...9999 s
  • Accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
  • Analogue input number 3
  • Analogue input type AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
  • Analogue output number 2
  • Analogue output type Software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits Software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
  • Base load current at high overload 1.5 A
  • Base load current at low overload 2.2 A
  • Brake chopper integrated True
  • Braking to standstill By DC injection
  • Connector type 2 RJ45 1 RJ45
  • Data format 8 bits, configurable odd, even or no parity Modbus serial
  • Depth 8.1 in (206 mm)
  • Discrete input logic Positive logic (source) DI1...DI8), < 5 V, > 11 V Negative logic (sink) DI1...DI8), > 16 V, < 10 V Positive logic (source) DI7, DI8), < 0.6 V, > 2.5 V Positive logic (source) STOA, STOB), < 5 V, > 11 V
  • Discrete input number 10
  • Discrete input type DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm DI7, DI8 programmable as pulse input 0…30 kHz, 24 V DC <= 30 V) STOA, STOB safe torque off, 24 V DC <= 30 V)> 2.2 kOhm
  • Discrete output number 2
  • Discrete output type Logic output DQ+ 0…1 kHz <= 30 V DC 100 mA Programmable as pulse output DQ+ 0…30 kHz <= 30 V DC 20 mA Logic output DQ- 0…1 kHz <= 30 V DC 100 mA
  • Electrical connection Control screw terminal 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal 2.5...6 mm² AWG 14...AWG 10 Motor screw terminal 2.5...6 mm² AWG 14...AWG 10 DC bus screw terminal 2.5...6 mm² AWG 14...AWG 10
  • Exchange mode Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
  • Height 13.8 in (350 mm)
  • Input compatibility DI1...DI8 discrete input level 1 PLC IEC 61131-2 DI7, DI8 pulse input level 1 PLC IEC 65A-68 STOA, STOB discrete input level 1 PLC IEC 61131-2
  • Isolation Between power and control terminals
  • Linearity error AI1, AI2, AI3 +/- 0.15 % of maximum value analog input AQ1, AQ2 +/- 0.2 % analog output
  • Local signalling Local diagnostic 3 LED mono/dual colour) Embedded communication status 5 LED dual colour) Communication module status 2 LED dual colour) Presence of voltage 1 LED red)
  • Maximum Input Current per Phase 1.5 A
  • Maximum output voltage 480.0 V
  • Maximum switching current Relay output R1 resistive, cos phi = 1 3 A 250 V AC Relay output R1 resistive, cos phi = 1 3 A 30 V DC Relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC Relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC Relay output R2, R3 resistive, cos phi = 1 5 A 250 V AC Relay output R2, R3 resistive, cos phi = 1 5 A 30 V DC Relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC Relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC
  • Method of access Slave Modbus TCP
  • Minimum switching current Relay output R1, R2, R3 5 mA 24 V DC
  • Motor slip compensation Not available in permanent magnet motor law Can be suppressed Automatic whatever the load Adjustable
  • Net weight 9.9 lb(US) (4.5 kg)
  • Number of addresses 1…247 Modbus serial
  • Physical interface Ethernet 2-wire RS 485
  • Power dissipation in W Natural convection 26 W 380 V 4 kHz Forced convection 21 W 380 V 4 kHz
  • Protection type Thermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive
  • Quantity per set 1
  • Refresh time Relay output R1, R2, R3)5 ms +/- 0.5 ms)
  • Relative symmetric network frequency tolerance 5 %
  • Relay output number 3
  • Relay output type Configurable relay logic R1 fault relay NO/NC 100000 cycles Configurable relay logic R2 sequence relay NO 1000000 cycles Configurable relay logic R3 sequence relay NO 1000000 cycles
  • Sampling duration 2 ms +/- 0.5 ms DI1...DI8) - discrete input 5 ms +/- 1 ms DI7, DI8) - pulse input 1 ms +/- 1 ms AI1, AI2, AI3) - analog input 5 ms +/- 1 ms AQ1, AQ2) - analog output
  • Supply External supply for digital inputs 24 V DC 19…30 V), <1.25 mA overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection Internal supply for digital inputs and STO 24 V DC 21…27 V), <200 mA overload and short-circuit protection
  • Transmission frame RTU
  • Transmission rate 10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial
  • Type of polarization No impedance Modbus serial
  • Width 5.7 in (144 mm)
  • With safety function Safe brake management (SBC/SBT) True
  • With safety function Safe Direction (SDI) False
  • With safety function Safe Operating Stop (SOS) False
  • With safety function Safe Position (SP) False
  • With safety function Safe programmable logic False
  • With safety function Safe Speed Monitor (SSM) False
  • With safety function Safe Stop 1 (SS1) True
  • With safety function Safe torque off (STO) True
  • With safety function Safely Limited Position (SLP) False
  • With safety function Safely Limited Speed (SLS) True
  • With sft fct Safe Stop 2 (SS2) False
  • Environment

  • Ambient air temperature for operation 5…122 °F (-15…50 °C) without derating) 122…140 °F (50…60 °C) with derating factor)
  • Ambient air temperature for storage -40…158 °F (-40…70 °C)
  • Ambient air transport temperature -40…158 °F (-40…70 °C)
  • Assembly style Enclosed
  • Electromagnetic compatibility Electrostatic discharge immunity test level 3 IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 Conducted radio-frequency immunity test level 3 IEC 61000-4-6
  • Environmental characteristic Chemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3
  • Environmental class (during operation) Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3
  • Insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
  • marking CE
  • Maximum acceleration under shock impact (during operation) 150 m/s² at 11 ms
  • Maximum acceleration under vibrational stress (during operation) 10 m/s² at 13...200 Hz
  • Maximum deflection under vibratory load (during operation) 1.5 mm at 2...13 Hz
  • Maximum THDI <48 % full load IEC 61000-3-12
  • Noise level 54.5 dB
  • Operating altitude <= 3280.84 ft (1000 m) without derating 1000...4800 m with current derating 1 % per 100 m
  • Operating position Vertical +/- 10 degree
  • Overvoltage category III
  • Permitted relative humidity (during operation) Class 3K5 according to EN 60721-3
  • Pollution degree 2
  • Product certifications CSA UL TÜV
  • Regulation loop Adjustable PID regulator
  • Relative humidity 5…95 % without condensation IEC 60068-2-3
  • Shock resistance 15 gn 11 ms IEC 60068-2-27
  • Standards UL 508C IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
  • Vibration resistance 1.5 mm peak to peak 2…13 Hz)IEC 60068-2-6 1 gn 13…200 Hz)IEC 60068-2-6
  • Volume of cooling air 10038.7 Gal/hr(US) (38 m3/h)
  • Packing Units

  • Number of Units in Package 1 1
  • Number of Units in Package 2 6
  • Package 1 Height 12.205 in (31.000 cm)
  • Package 1 Length 16.142 in (41.000 cm)
  • Package 1 Weight 12.846 lb(US) (5.827 kg)
  • Package 1 Width 7.480 in (19.000 cm)
  • Package 2 Height 29.528 in (75.000 cm)
  • Package 2 Length 31.496 in (80.000 cm)
  • Package 2 Weight 105.738 lb(US) (47.962 kg)
  • Package 2 Width 23.622 in (60.000 cm)
  • Unit Type of Package 1 PCE
  • Unit Type of Package 2 P06
  • Ordering and shipping details

  • Category US1CP4E22276
  • Country of origin ID
  • Discount Schedule CP4E
  • GTIN 3606480883255
  • Returnability Yes

Write a review

Note: HTML is not translated!
    Bad           Good
variable speed drive, Altivar Process ATV900, ATV930, 0.75kW, 400 to 480V, with braking unit, IP21

variable speed drive, Altivar Process ATV900, ATV930, 0.75kW, 400 to 480V, with braking unit, IP21

0.00ريال